Air for combustion and ventilation – Desa VF-24N-BTB User Manual

Page 7

Advertising
background image

www.desatech.com

111826-01G



1. Determine the volume of the space (length x

width x height).

Length x Width x Height =__________cu. ft.

(volume of space)

Example:

Space size 20 ft. (length) x 16 ft.

(width) x 8 ft. (ceiling height) = 2,560 cu. ft.

(volume of space)

If additional ventilation to adjoining room is

supplied with grills or openings, add the volume

of these rooms to the total volume of the space.

2. Multiply the space volume by 20 to determine

the maximum Btu/Hr the space can support.

__________ (volume of space) x 20 = (Maxi-

mum Btu/Hr the space can support)

Example:

2,560 cu. ft. (volume of space) x 20 =

51,200 (maximum Btu/Hr the space can support)

3. Add the Btu/Hr of all fuel burning appliances in

the space.

Vent-free fireplace

__________ Btu/Hr

Gas water heater*

__________ Btu/Hr

Gas furnace

__________ Btu/Hr

Vented gas heater

__________ Btu/Hr

Gas fireplace logs

__________ Btu/Hr

Other gas appliances* + __________ Btu/Hr

Total

= __________ Btu/Hr

* Do not include direct-vent gas appliances. Di-

rect-vent draws combustion air from the outdoors

and vents to the outdoors.

Example:

Gas water heater

__________ Btu/Hr

Vent-free fireplace

+ __________ Btu/Hr

Total

= __________ Btu/Hr

4. Compare the maximum Btu/Hr the space can

support with the actual amount of Btu/Hr used.

_________Btu/Hr (maximum the space can support)

_________ Btu/Hr (actual amount of Btu/Hr used)

Example:

51,200 Btu/Hr (maximum the space

can support)

73,000 Btu/Hr (actual amount of

Btu/Hr used)

The space in the example is a confined space because

the actual Btu/Hr used is more than the maximum

Btu/Hr the space can support. You must provide ad-

ditional fresh air. Your options are as follows:

A. Rework worksheet, adding the space of an adjoin-

ing room. If the extra space provides an unconfined

space, remove door to adjoining room or add

ventilation grills between rooms. See Ventilation

Air From Inside Building.

B. Vent room directly to the outdoors. See Ventila-

tion Air From Outdoors, page 8.

AIR FOR COMBUSTION

AND VENTILATION

Continued

40,000

33,000

73,000

C. Install a lower Btu/Hr fireplace, if lower Btu/Hr

size makes room unconfined.

If the actual Btu/Hr used is less than the maximum

Btu/Hr the space can support, the space is an uncon-

fined space. You will need no additional fresh air

ventilation.

WARNING: If the area in

which the heater may be oper-

ated is smaller than that defined

as an unconfined space or if the

building is of unusually tight

construction, provide adequate

combustion and ventilation air

by one of the methods described

in the National Fuel Gas Code,

ANSI Z223.1/NFPA 54 Section 5.3

or applicable local codes.

vENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining un-

confined space. When ventilating to an adjoining

unconfined space, you must provide two permanent

openings: one within 12" of the ceiling and one

within 12" of the floor on the wall connecting the

two spaces (see options 1 and 2, Figure 2). You

can also remove door into adjoining room (see

option 3, Figure 2). Follow the National Fuel Gas

Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for

Combustion and Ventilation for required size of

ventilation grills or ducts.

Figure 2 - Ventilation Air from Inside

Building

Or

Remove

Door into
Adjoining

Room,
Option

3

Ventilation Grills

Into Adjoining Room,

Option 2

Ventilation

Grills

Into Adjoining

Room,

Option 1

12"

12"

Advertising
This manual is related to the following products: