4 termination, 1 termination resistors, 2 biasing resistors – Bronkhorst FLOW-BUS interface User Manual

Page 15: Ermination, Termination resistors, Biasing resistors

Advertising
background image

BRONKHORST

®

 

Page 15   

 

 

 

 

FLOW‐BUS interface 

 

 

 

9.17.024 

2.4 T

ERMINATION

 

 
For best quality of data transfer FLOW‐BUS should be terminated correctly. 
 

2.4.1 Termination resistors 

A  resistor  is  added  in  parallel  with  the  receiver’s  “A”  and  “B”  lines  in  order  to  match  the  data  line  characteristic 
impedance  specified  by  the  cable  manufacturer  (120  Ω  is  a  common  value).  This  value  describes  the  intrinsic 
impedance of the transmission line and is not a function of the line length. A terminating resistor of less than 90 Ω 
should not be used. Termination resistors should be placed only at the extreme ends of the data line (see Termination 
schematics resistors RT1 and RT2), and no more than two terminations should be placed in any system that does not 
use repeaters. 
 

2.4.2 Biasing resistors 

When an RS‐485 network is in an idle state, all nodes are in listen (receive) mode. Under this condition there are no 
active drivers on the network. All drivers are tri‐stated. Without anything driving the network, the state of the line is 
unknown. If the voltage level at the receiver’s A and B inputs is less than ±200 mV the logic level at the output of the 
receivers will be the value of the last bit received. In order to maintain the proper idle voltage state, bias resistors 
must be applied to force the data lines to the idle condition. Bias resistors are nothing more than a pull‐up resistor 
(RB1) on the data RS485‐A line and a pull‐down (to ground) on the data RS485‐B line. The “Termination schematic” 
illustrates the placement of bias resistors on a transceiver. The value of the bias resistors is dependent on termination 
and number of nodes in the system. The goal is to generate enough DC bias current in the network to maintain a 
minimum of 200 mV between the B and A data line. Consider the following example of bias resistor calculation. 
 
Ideal situation: 
Termination resistors: 

120 Ohm 

Receiver resistance: 

omitted 

Bias supply voltage: 

5Vdc 

Wanted situation is a minimum of 200mV between A and B lines and a common mode voltage of 2.5V. 
 
Minimum current therefore: 

 

 

200mV / 60 Ohm = 3.33mA 

Total maximum bias resistor value is 

 

(5V – 0.2V)/3.33mA = 1440 Ohm. 

The maximum value of each biasing resistor: 

720 Ohm. 

 
Situation with 127 nodes: 
Termination resistors: 

120 Ohm 

Receiver resistance: 

12 KOhm 

Number of instruments:  127 
Bias supply voltage: 

5Vdc 

Wanted situation is a minimum of 200mV between A and B lines and a common mode voltage of 2.5V. 
 
Total termination resistance: 

 

 

120 // 120 // 12000* 127 = 120 // 120 // 94.5 = 36.7 Ohm 

Minimum current therefore: 

 

 

200mV / 36.7 Ohm = 5.45mA 

Total maximum bias resistor value is 

 

(5V – 0.2V)/5.45mA = 880 Ohm. 

The maximum value of each biasing resistors: 

440 Ohm. 

Lower values may be used. (Depending on maximum power consumption of the resistors) 
  
 

Bronkhorst advices the following resistor values for the following voltages. 

Supply voltage 

termination 

Termination 

resistors 

Bias Pull‐up 

resistor 

Bias Pull‐down 

resistor 

+5V 

121 Ohm 

392 Ohm 

392 Ohm 

+10V 

121 Ohm 

1210 Ohm 

392 Ohm 

+15V 

121 Ohm 

2210 Ohm 

392 Ohm 

+24V 

121 Ohm 

3480 Ohm 

392 Ohm 

 
 

Advertising