Bronkhorst  offers  special  begin‐termination  connectors  with  the  resistor  network.  This  handles  correct  termination 
but also gives a defined voltage on the RS485‐A and ‐B line for even more reliability of the bus system. 
An end‐terminator is also offered by Bronkhorst and handles correct termination ad the end of the bus. 
 
 
Termination can be performed with special termination‐connectors, offered by Bronkhorst. 

Termination schematic 

RJ45 

M12 

703297‐‐RJ45 Begin 

terminator 

703298‐‐RJ45 End 

terminator 

Begin terminator 

End terminator 

FLOW‐BUS system 

Page 16   

 

 

 

 

FLOW‐BUS interface 

 

 

 

9.17.024 

 
At  the  beginning  of  each  FLOW‐BUS  system  there  always  must  be  a  resistor  network  as  showed  above.  This  begin‐
terminator needs to be part of your system. Bronkhorst offers special begin‐termination connectors with the resistor 
network. This handles correct termination but also gives a defined voltage on the RS485‐A and ‐B line for even more 
reliability of the FLOW‐BUS system. 
 
Bronkhorst advises always to use a termination resistor at the end of the bus in your system. This end‐terminator is 
also offered by Bronkhorst and handles correct termination for the FLOW‐BUS. 

+15…24Vdc 

RB1
976 Ohm 

RS485‐A

RT1
121 Ohm 

RB2
392 Ohm 

RS485‐B

RT2
121 Ohm 

Begin termination (RED) 

End termination (BLACK)