Input Signal

20-100 kPa/3-15 Psi (6-30 optional)

4-20 mA

Linearity

≤ 0,5%*

≤ 0,5%*

Hysteresis

≤ 0,75%*

≤ 0,5%*

Repeatability

≤ 0,5%*

≤ 0,5%*

Gain

(pressure 600 kPa/87 Psi)
1 000 (kPa/kPa)
Min 66%/% ISA S75.13

Air consumption at Supply pressure:
0,2 MPa/29 Psi

5,4 nl/min 0.19 SCFM

6,1 nl/min 0.22 SCFM

0,4 MPa/58 Psi

12,3 nl/min 0.43 SCFM

13,6 nl/min 0.48 SCFM

0,6 MPa/87 Psi

20 nl/min 0.71 SCFM

22 nl/min 0.78 SCFM

0,8 MPa/116 Psi

27,8 nl/min 0.98 SCFM

30,5 nl/min 1.08 SCFM

1 MPa/145 Psi

35,7 nl/min 1.26 SCFM

39 nl/min 1.38 SCFM

Air delivery at Supply Pressure:
0,2 MPa/29 Psi

200 nl/min 6.9 SCFM

0,4 MPa/58 Psi

370 nl/min 12.8 SCFM

0,6 MPa/87 Psi

540 nl/min 18.8 SCFM

0,8 MPa/116 Psi

710 nl/min 24.7 SCFM

1 MPa/145 Psi

880 nl/min 30.6 SCFM

Supply Pressure Max 1 MPa/150 Psi

0,15-1 MPa/21,8-150 Psi

Temperature range -20

°C to +85°C (-4°F to 185°F)

Connector threads

1/4" NPT or G

Gauge threads

1/8" NPT or G

Weight std.

1,1 kg/2.4 lbs

1,5 kg/3.4 lbs

Weight with gauges 1,3 kg/2.9 lbs

1,8 kg/3.9 lbs

Ingress protection

IP 66/NEMA 4

* Per cent of full scale.