Recommended installation – Flowserve IOM Control Valves User Manual

Page 19

Advertising
background image

19

EN

• Are the piping flanges equiaxial and parallel and does the

distance between pipe ends correspond to the valve length?

If not, excessive tension, valve malfunctions and leaks at the flange connections

may result.

• Is the piping routed correctly and is the valve free from

additional piping forces?

If not, leaks may develop and, depending on the situation, the valve may fail.

• Is the installation position of the valve with vertical valve

spindle achieved?

If not, increased wear in the stuffing box packing, leaks and, depending on the

situation, rubbing may occur.

Contact the manufacturer if the prevailing installation conditions mean that the

valve will have to be fitted horizontally.

• Is there a suitable surge section upstream and downstream

of where the valve is installed?

The absence of a surge section can create critical operating conditions and

cause impermissible levels of noise and vibration!

• Is appropriate equipotential bonding provided?

Impermissible electrical compensating currents across the valve and the actuator

can generate static and cause electrical discharging.

In explosive atmospheres, the only valves that may be used

are those that comply with the permitted group, equipment

category and temperature class requirements laid down in

Directive 94/9/EC (ATEX)!

Recommended installation

Successful use of the control valve is conditional on

the availability of a suitable installation environment.

We suggest that the recommended values be adhered to, as it is very important to take

account of physical aspects when using the control valve. Deviations can result in significant

control deviations, and in the worst case expensive rerouting of the piping will be necessary.

However, some physical processes will permit a deviation from these values, although in such

cases system knowledge is required, as is the express approval of the manufacturer.

Recommended installation for

control valves

Control valve

Dirt trap

(0.1 mm)

Medium

Installation distance from valve

10 x DN

(at least 1m)