Trouble shooting - continued, Defect no. possible causes remedy – Flowserve IOM Control Valves User Manual

Page 24

Advertising
background image

4

EN

Trouble shooting - continued

Defect

No. Possible causes

Remedy

Excessive valve-seat leakage

4.1

4.2

4.3

• damaged sealing edges at valve

seat or plug

• foreign particles in seat area

• plug does not close fully

• contact customer services department or

contract partner

• contact customer services department or

contract partner

• refer to 3.1 to 3.5

Leaking stuffing box system

5.1

5.2

5.3

5.4

• compression force on packing too

low

• worn packing

• dirty spindle

• damaged spindle

• slightly re-tighten stuffing box packing

Caution:

make sure the valve spindle

can still move!

• slightly re-tighten stuffing box packing

Caution:

make sure the valve spindle

can still move!

if the packing does not stop leaking, contact

customer services department or contract

partner

• clean spindle with suitable cleaning agent

• contact customer services department or

contract partner

Leaking top or lid seal

6.1

6.2

• pressing force on seal(s) too low

• seals(s) defective

• properly re-tighten top or lid nuts crosswise

• contact customer services department or

contract partner

Leaking housing

7.1

• medium- or flow-related damage

• contact customer services department or

contract partner

No limit switch signal

8.1

8.2

• power supply to limit switch

interrupted

• limit switch misadjusted

• check power supply (connections, circuit

breakers, voltage)

• readjust limit switch; operating distance see

limit switch data sheet

Vibrating positioner

9.1

• defective positioner

• see maintenance and operating instructions of

positioner manufacturer

If the problem is not solved by taking the above measures, contact the customer services

department or contract partner.