Flowserve 132000 LinedFlow Linear Lined Globe Control Valve IOM User Manual

Page 4

Advertising
background image

®

User Instructions LinedFlow - KMENIM3202-02 01/12

4

DaNgER: Do not install valves whose approved pressure

and temperature range is not sufficient for the operating

conditions. The limits for use are marked on the valves.

Moreover, use only valves suitable for the operating medium

in question.

Failure to observe these precautions can pose a danger for

the user and cause damage to the piping system.

5.2

The actuator must correspond to the intended connections

and control data.

5.3

The connection flanges must be inline with the valve

connections and parallel. connection flanges which are not
parallel can damage the plastic liner during installation!

5.4

Before installing, thoroughly clean the valve and the pipeline

to remove any contamination, particularly hard foreign parti-

cles.

5.5

In particular, it is necessary to ensure that the sealing sur-

faces on the flange connection are free of all contamination

when installing.

5.6

When inserting the valve into a pipeline already installed, the

distance between the ends of the pipeline must be sufficient

to prevent damage to any of the sealing surfaces.

WaRNINg:

Tighten all flange connections to the torques

specified in Tables 1a or 1b. When using torque wrenches,

ensure that these torques are reached, however not excee-

ded.

The values in the table apply for flanges according to

EN1092, PN10/16 for a maximum operating pressure of

10 bar. Values for other flanges can be obtained from the

manufacturer.

5.7

Valves are to be installed in the appropriate flow direction.

The flow direction is indicated by an arrow on the valve.

5.8

Observe the appropriate instructions for connecting the

actuator to the valve. Control valves are equipped with a

positioner. The connections for air supply and signals are

marked clearly (see also applicable operating instructions for

the positioner). The maximum air supply is specified on the

name plate. If the air supply exceeds the pressure specified

on the rating plate, a pressure reduction station is required.

If no instrument air is available, install an air filter in the air

supply line if required.

5.9

After completion of installation, perform a function test with

the control signals: The valve should open and close properly

corresponding to the control commands. Always eliminate

any recognizable malfunctions before startup. See also

applicable sections in maintenance regulations for this valve

series.

DaNgER:

Improperly executed control commands can pose

a danger for life and limb and damage to the piping system

and/or the valve.

6

PRESSURE TESTINg PIPINg SEcTION

The valve has already been pressure-tested by the manuf-

acturer. When pressure testing a section of the pipeline with

valves installed, observe the following:

6.1

First thoroughly flush newly installed piping systems to

remove all foreign objects.

6.2

Valve opened: The test pressure should not exceed the

value of 1.5 x PN (according to nameplate):

6.3

Valve closed: The test pressure should not exceed the value

1.1 x PN (according to nameplate).

If a leak occurs on the valve, observe Section 8 “Trouble-

shooting”.

caUTION: If the flange connection with plastic liner leaks:

First retighten flange connection to torque specified in Table

1a or 1b in Section 5.6 (installation).

If the flange connection is still leaks:

Loosen flange connection. Check the flange connection to

ensure that it is smooth and parallel.

Check the sealing surfaces on both flanges: When the inner

lining is damaged, replace valve and/or counterflange.

STOP!

Table 1a: Tightening Torques for Flange connections, Flanges EN1092 (DIN)

DN [mm]

15

20

25

40

50

80

100

150

M

A

[Nm]

10

18

25

50

65

65

65

140

Table 1b: Tightening Torques for Flange connections, Flanges EN1759 (aNSI)

NW [inch]

½"

¾"

1"

1½"

2"

3"

4"

6"

M

A

[Nm]

8

11

15

26

60

100

76

100

Advertising