3 segment compliance voltage – Flowserve 3400IQ Digital Positioner User Manual

Page 20

Advertising
background image

Logix 3400IQ Digital Positioner FCD LGENIM3401-00 – 06/06

0

Figure 6: Field Termination

Shielded Cable

FF Signal

Connect Shield at Source

Housing EARTH

Terminal

External

Bonding

Location

FF Field

Terminators

Environmental

Seal

c

WARNING: The green grounding screw must not be used to terminate signal shield wires.

6.3

Segment Compliance Voltage

(See Figure 7)

Output compliance voltage refers to the voltage limit that can be provided by the FF source. A FF
system consists of the FF source, wiring resistance, barrier resistance (if present), and the Logix
3400IQ positioner voltage. The Logix 3400IQ digital positioner requires that the system allows for a
9.0 VDC drop across the positioner at minimum segment voltage. The actual voltage at the terminals
varies from 9.0 to 32.0 VDC depending on the FF signal and ambient temperature.

Determine if the segment will support the Logix 3400IQ digital positioner by performing the following
calculation.

Voltage = Compliance Voltage (@ 23 mA) –

23 mA • (R

barrier

+ R

wire

)

Equation 1