4 cable requirements, 5 intrinsically safe barriers, 6 dd support – Flowserve 3400IQ Digital Positioner User Manual

Page 21

Advertising
background image

1

Logix 3400IQ Digital Positioner FCD LGENIM3401-00 – 06/06

flowserve.com

The calculated voltage must be greater than 9 VDC in order to safely support the Logix 3400IQ digital
positioner.

Example:

DCS Compliance Voltage = 19 VDC

R

barrier

= 300 Ω

R

wire

= 25 Ω

Current

max

= 23 mA

Voltage = 19 VDC – 0.023 A • (300 Ω + 25 Ω) = 11.5 VDC

The voltage 11.5 VDC is greater than the required 9.0 VDC; therefore, this system will support the
Logix 3400IQ

digital positioner.

Figure 7: Compliance Voltage

+

-

R

barrier

(if present)

R

wire

FF

Signal

Source

Compliance

Voltage

Logix

3400IQ

Current

23 mA

9 VDC min

6.4

Cable Requirements

The Logix 3400IQ digital positioner utilizes the FF protocol. This communication signal is superim-
posed on the supply voltage.

FF rated cable should be used. Refer to H1 wiring specification.

6.5

Intrinsically Safe Barriers

When selecting an intrinsically safe barrier, make sure the barrier is FF compatible. Although the
barrier will pass the segment voltage and allow normal positioner operation, if not compatible, it may
prevent FF communication.

6.6

DD Support

The DD for the Logix 3400IQ can be downloaded from either the flowserve website: www.flowserve.
com or the F

oundation

Fieldbus website: www.Fieldbus.org.

Advertising