Maintenance – Flowserve HV 215 User Manual

Page 34

Advertising
background image

34

Bottom valves HWV 205/1 - DN 80/ HWV 215/1 - DN 80

Maintenance

Type of maintenance

Time interval

Activity

Check
valve plug seal

When necessary,

during main inspection

at the latest (every 4 yrs.)

Check valve head for leaks.

If a leak is detected replace valve plug seal

as described in section “Maintenance”.

Replace
valve plug seal

Main inspection

(every 4 yrs.)

Replace valve plug seal as described

in section “Maintenance”.

Check
actuating cylinder

B

When necessary,

during main inspection

at the latest (every 4 yrs.)

Check connection between actuating

cylinder and body. If you detect an oil leak

replace the PTFE seal and the O-ring

as described in section “Maintenance”.

Check
torque of 50 Nm

$

When necessary,

during main inspection

at the latest (every 4 yrs.)

Check the torques of the four hexagon-head cap screws

of the actuating cylinder and, if necessary, retighten the

screws to a torque of 50 Nm.

Check
torque of 20 Nm

b

When necessary,

during main inspection

at the latest (every 4 yrs.)

Check and, if necessary, re-tighten the six hexagon-head

cap screws of the body and the two hexagon nuts that fix

the control unit to the body with a torque of 20 Nm.

Check
smoothness of operation
of ball valve shaft

When necessary,

during main inspection

at the latest (every 4 yrs.)

Check smooth operationg of switching shaft.

If the switching shaft does not move smoothly apply

a commercially available lubricant.

Replace
piston seal

(

When necessary,

every 8 years at the latest

Replace piston seal

as described in section “Maintenance”.

31

34

31

36

Advertising