Worcester controls – Flowserve Factory Mutual Approved Oil or Gas Safety Shutoff Valve User Manual

Page 13

Advertising
background image

WCAIM2054

Factory Mutual Approved Oil or Gas Safety Shutoff Valves

13

Factory Mutual Approved Oil and Gas
Safety Shutoff Valve Specifications

Valve Size:

Z|v"–2" Reduced Port, Three-Piece (44)

Z|v"–4" Full Port, Three-Piece (59)
2"–8" Reduced Port, Flanged (51/52)
3"–4" Reduced Port, Flangeless (4-151)

Materials:

All Carbon Steel
All Stainless Steel
Carbon Steel with Stainless Steel or Hastelloy C Ball and Stem

Valve End Configurations:

Z|v"–2" Reduced Port (44) and Z|v"-4" Full Port (59):

Screwed End, Butt Weld and Socket Weld

2"–8" Reduced Port:

150# Flanged (51)
300# Flanged (52)

3"–4" Reduced Port:

150# Flangeless (4–151)

Seats:

TFE or Reinforced TFE

Body Seals:

TFE or Buna

Stem Seals:

Polyfill with PEEK Protector or Reinforced TFE

Pressure Ratings:

Unheated No. 4 and Lighter Oil, Natural or LP Gas Service @
100°F Max:

950 PSI:

Z|v"–2" (44/59), Fluoropolymer Seats

1,450 PSI:

Z|v"–2" (44-59), Reinforced Fluoropolymer Seats

285 PSI: C.S. 3"–4" (4–151), 2"–8" (51)
275 PSI: S.S. 3"–4" (4–151), 2"–8" (51)
740 PSI: C.S. 2"–8" (52), 3"–4" (59)
720 PSI: S.S. 2"–8" (52), 3"–4" (59)

Heated No. 5 or 6 Oil, 300°F Maximum:

400 PSI:

Z|v"–2" (44/59), Fluoropolymer Seats

600 PSI:

Z|v"–2" (44/59), Reinforced Fluoropolymer Seats

225 PSI: C.S. 3"–4" (4–151), 2"–8" (51)
210 PSI: S.S. 3"–4" (4–151), 2"–8" (51)
425 PSI: 2"–8" (52), 3"–4" (59) Fluoropolymer Seats
640 PSI: C.S. 2"–8" (52), 3"–4" (59) Reinforced
Fluoropolymer Seats
560 PSI: S.S. 2"–8" (52), 3"–4" (59) Reinforced
Fluoropolymer Seats

Pressure rating is dependent upon temperature. Refer to
published pressure/temperature curves for appropriate rating.

Actuator:

10-3539S For

Z|v"–2" (44/59/51/52)

30-4039S For 3"–4" (4-151)
30-4239S For 3"–8" (51/52) and 3"–4" (59)

Actuator Pressure Ratings:

Z|v"–6" Valve Sizes: 60-120 PSI
(Actuator time to be 5 seconds or less to close valves)

Ambient Temperatures:

+50°F To +150°F, Valves with 3039S Actuators
0°F To +150°F, For all Valves with Other Actuator Sizes

Voltages (Solenoid):

24, 120, 240 VAC / 12, 24 VDC

Nema Rating (Solenoid):

Type 1 – General Purpose
Type 4X, 7, 9 – Watertight and Hazardous Locations, Class I,
Groups A, B, C and D; Class II, Groups E, F and G

Mounting:

All actuators are factory mounted in-line, fail-close.

End-Mounted Limit Switch (Elk) Option:

Switch Options:

Z-SPDT, ZD – DPDT, Z1 – AC Proximity,
Z3 – DC Proximity

Enclosure:

Type 4, 7, 9 – Watertight and
Hazardous Locations,
Class I, Groups C and D; Class II,
Groups E, F and G

Flow Control Division

Worcester Controls

Advertising