Factory Mutual Approved Oil or Gas Safety Shutoff Valves

WCAIM2054

CAUTION: Flowserve recommends that all products which must be
stored prior to installation be stored indoors, in an environment
suitable for human occupancy. Do not store product in areas where
exposure to relative humidity above 85%, acid or alkali fumes,
radiation above normal background, ultraviolet light, or
temperatures above 120°F or below 40°F may occur. Do not store
within 50 feet of any source of ozone.

I. INSTALLATION

A.

Z|v"–2" 44 Series Reduced-Port and Z|v"–4" 59 Series Full-Port
Valves, Three-Piece Construction:

1. Standard valves may be installed for flow in either direction.

Use care to exclude pipe sealants from the valve cavity.

2. For weld-end valves:

NOTE: Prior to welding or brazing, THOROUGHLY CLEAN ALL
JOINT SURFACES to prevent contamination.

a. Tack weld valve in place.

b. Rotate valve stem 90° to open valve.

c. Remove actuator, bracket and coupling, if necessary.

d. For

Z|v"–2" valves, remove three body bolts and loosen

fourth. Swing valve body away from pipe ends. For 3" and
4" 59 valves, remove all of the body bolts or studs and
remove center section from valve.

e. Close valve, then remove seats, body seals and ball.

f. Swing or return body back in-line and secure with two

body bolts or studs diagonally opposite each other.

g. Weld valve in place (when gas welding or brazing, do not

play flame on valve body).

h. Allow valve to cool, then reassemble. Take care that interior

of valve is free of dirt particles. Do not scratch any sealing
surfaces (ball, seats, body seals or pipe end faces).

i. Reassemble ball, seats and seals into body. Install new

body seals, if they were shipped separately from the
valve. Temporary Buna body seals, found in the valve as
received, are not to be reused. Open valve. Swing body
back in-line. Close valve.

j. Install body bolts or studs.

k. Remount actuator to valve, if removed. (Insert coupling

between valve and actuator.)

l. The body bolts of the valve should be tightened evenly.

Tighten diagonally opposite each other alternating in a
criss-cross pattern. Use torque figures listed:

For Carbon Steel Bolts

Bolt Diameter

In.-Lbs.

Ft.-Lbs.

Z|v"

96-120

8-10

B|zn"

156-204

13-17

C|,"

216-264

18-22

M|zn"

480-540

40-45

Z|x"

720-780

60-65

>|zn"

1080-1140

90-95

B|,"

1370-1420

114-119

C|v"

1800-1860

150-155

For Stainless Steel Bolts

Bolt Diameter

In.-Lbs.

Ft.-Lbs.

Z|v"

72-94

6-8

B|zn"

120-144

10-12

C|,"

192-216

16-18

M|zn"

336-384

28-32

Z|x"

504-552

42-46

>|zn"

682-730

57-61

B|,"

972-1020

81-85

C|v"

1402-1450

117-121

CAUTION: In

Z|v"-2" 44 and Z|v"-1Z|x" 59 valves, TFE seals are not

reusable. Upon disassembly of the valve, they should be discarded
and replaced with new parts. New valves are shipped with Buna
seals installed and TFE seals packaged. Care should be taken to
avoid scratching the TFE seals during installation. Light lubrication
of these seals can help to prevent damage.

B. 2"–8" 51/52 Flanged Valves and 3" and 4" 4 (151) Flangeless

Valves:

1. Standard valves may be installed for flow in either direction.

Use care to exclude pipe sealants from the valve cavity.

2. When installing, use standard gaskets suitable for the specific

service. Tighten flange bolts or studs evenly.

3. On 4 (151) flangeless valves, it is recommended to leave the

ball in the open position while installing, to eliminate
possibility of damaging ball finish.

C. 39S

Actuator:

a

WARNING: Series 39 actuators are electromechanical devices

subject to normal wear and tear. Actuator life is dependent upon
application and environmental conditions. If applied in hazardous
services such as, but not limited to, media temperature extremes,
toxins, flammables, or other services where improper or
incomplete operation could produce a safety hazard, it is
incumbent upon the system designer and the user to provide proper
warning devices such as temperature sensors, oxygen sensors and
flow sensors. Flowserve also recommends that the optional
auxiliary limit switches be used for monitoring and/or electrical
interlock.