Modular Accessory System (Series 90)

07334-F

I. INTRODUCTION

The MODULAR ACCESSORY SYSTEM SERIES 90 (OR 90 M.A.S.) is
designed to provide a wide choice of valve position feedback and
pneumatic valve actuator control functions. Applications range from
simple end-of-travel limit switch indication to automated control using
feedback from a system parameter sensor (temperature, flow rate,
etc.). Maximum ambient temperature is 110°F for models with
solenoid and 160°F for models with electronics and no solenoid.

The concept behind the unit is flexibility, allowing the user to
customize a M.A.S. for a particular application. For this reason, only
individual installation instruction sheets pertaining to the specific
options being used are combined with this Installation, Operation
and Maintenance Manual. Please note – this unit is a complex
device and not all options can be accommodated simultaneously. A
table summarizing the available options follows. Note that the
presence of the POSITIONER or CONTROLLER options changes the
list of available options. Certain options also require the addition of
a second terminal block which will be provided in the M.A.S. unit or
kit when required.

a

WARNING: The series 90 M.A.S. is an electromechanical device

subject to normal wear and tear. Its life is dependent upon
application and environmental conditions. Breather/Drain fittings
are recommended for humid environments when moisture may
condense inside the sealed M.A.S. housing.

CAUTION: Flowserve recommends that all product that must be
stored prior to installation be stored indoors, in an environment
suitable for human occupancy. Do not store product in areas where
exposure to relative humidity above 85%, acid or alkali fumes,
radiation above normal background, ultraviolet light, or
temperature above 120°F or blow 40°F may occur. Do not store
within 50 feet of any source of ozone.

M.A.S. MODEL: The M.A.S. product code per the appropriate options is

marked on the name plate as the M.A.S. model
number, with the exception of the voltage rating (if
any) and product revision level (R#). Voltage rating and
R# are marked in separate locations on the nameplate.

The Product Code is Composed of:

Size . . . . . . . . . . . . . . . . Size of actuator (10, 15, 20, etc.) to which

the M.A.S. will be mounted. Will be blank if
unknown.

Product Options . . . . . . See below.

Product Series . . . . . . . . 90

Action . . . . . . . . . . . . . . blank – if no solenoid

S – single-acting solenoid
D – double-acting solenoid

Direction . . . . . . . . . . . . blank – if standard

R – if reverse-acting

Switch Options . . . . . . . See below.

Circuit Board . . . . . . . . . P – Positioner

C – Controller
Blank if none

Input Signal . . . . . . . . . 1 – 1-5 mA
(If P or C is used)

4 – 4-20 mA
10 – 10-50 mA
13 – 0-135 ohms
1K – 0-1000 ohms

Setpoint . . . . . . . . . . . . . 4 – 4-20 mA
(If Controller)

K – 0-1000 ohms

Custom Product No. . . . P, T, C, or similar number
(If special)

Product Code Examples:

20 H 90 D M2 C 4 K
10 90 S P6 T3293

Flow Control Division

Worcester Controls

Available Options

Non-Positioner/Controller Units

Positioner/Controller Units

Order Codes and Descriptions

Order Codes and Descriptions

B – Breather/Drain Fitting

H – Heater

D – Dual-Feedback Potentiometer
P – Single-Feedback Potentiometer
4 – 4 to 20 Milliamp Feedback

S – Single-Acting Solenoid Block

(One Three-Way Solenoid)

D – Double-Acting Solenoid Block

(One Four-Way Solenoid)

M2 – 2 SPDT Mechanical Switches
M4– 4 SPDT Mechanical Switches
D2 – 2 DPDT Mechanical Switches
P6 – 2 AC Proximity Switches
P8 – 2 DC Proximity Switches

120A – 120 Volt AC Solenoid
12D – 12 Volt DC Solenoid
24D – 24 Volt DC Solenoid

B – Breather/Drain Fitting

H - Heater

P – Single-Feedback Potentiometer
4 – 4 to 20 Milliamp Feedback

S – Single-Acting Solenoid Block

(Two Three-Way Solenoids)

D – Double-Acting Solenoid Block

(Two Three-Way Solenoids)

M2 – 2 SPDT Mechanical Switches

P6 – 2 AC Proximity Switches
P8 – 2 DC Proximity Switches

120A – 120 Volt AC Solenoids
12D – 12 Volt DC Solenoids
24D – 24 Volt DC Solenoids

P – Positioner Circuit Board

(Various Input Signal Options)

C – Controller Circuit Board

(Various Input Signal and Set Point Options)