Wiring – Flowserve NRG 26-40 User Manual

Page 17

Advertising
background image

7

Wire equipment in series. Star-type wiring is not permitted!

Interlink screens of control cables such that electrical continuity is ensured and

connect them

once to central earthing point (CEP).

In a CAN bus network the first and the last equipment

must be provided with a

terminating resistor of 20

Ω. Fig. 11

The CAN bus network mut

not be interrupted while operating.

An interruption will result in high/low level alarm.

Tools

Attention

Screwdriver for cross head screws, size 

Screwdriver for slotted screws, size 2.5, completely insulated according to VDE 0680

Open-end spanner 7 mm A. F.

Wiring

continued