Technical data – Flowserve NRG 26-40 User Manual
Page 6
6
NRG 26-40
Type Approval Nº
TÜV · WR · 04-399
Max. service pressure
32 bar g at 238°C
Connections
Screwed ¾" BSP, EN ISO 228-
Materials
Case: Die cast aluminium 3.26 (G AlSi8Cu3)
Stem: S. S. .457 (X6CrNiMoTi7-2-2)
Measuring electrodes: S. S. .440 (X5CrNiMo7-2-2)
Electrode insulation: PTFE
Length supplied/measuring range
see
Fig. 2
Supply voltage
8 – 36 V DC
Current consumption
65 mA
Fuse
Thermal fuse T
max
= 80 °C
Hysteresis
-2 K
Data exchange
CAN bus acc. to DIN ISO 898, CANopen protocol
Attenuation, signal output
9 sec.
Indicators and adjustors
green LED “C
an
bus
CommuniCation
”
red LED “b
us
fault
”
0-pole code switch for node ID and baud rate settings
Electric connection
M 2 sensor connector, 5 poles, A-coded,
M 2 sensor jack, 5 poles, A-coded
Protection
IP 65 to DIN EN 60529
Max. admissible ambient temperature
70 °C
Weight
approx. 2.5 kg
Technical data