9

Basic Settings

continued

H

1

1 2 3

5 6 7

4

8 910

ON

1

2

3

4

5

Fig. 12

Attention

Do

not assign the same node ID twice within the CAN bus network.

Assigning / changing node ID

If several systems of the same kind are to communicate in one CAN bus network, be sure to establish

one node ID for each individual system component (e. g. controller).
. Undo screws

E and remove housing cover G.

2. Change code switch

H settings as required. For more information refer to page 20.

3. Re-attach housing cover

G and fix it with screws E.

H

Factory set default node IDs

NRS 1-40 ID: 001

NRS 1-40.1 ID: 001

NRS 1-41 ID: 006

NRS 1-42 ID: 020

NRS 2-40 ID: 039

NRR 2-40 ID: 040

LRR 1-40 ID: 050

NRG 16-40 ID: 002

NRG 16-40 ID: 003

NRG 16-41.1 ID: 004

TRV 5-40

ID: 005

NRG 16-41 ID: 007

NRG 16-42 ID: 021

NRG 26-40 ID: 041

LRG 16-40 ID: 051