Flowserve NRG 26-40 User Manual

Page 5

Advertising
background image

5

Explanatory Notes

continued

Description

The level electrode NRG 26-40 works according to the capacitance measurement principle.

The NRG 26-40 is used for signalling different levels in conductive and non-conductive liquids:

Water level maintained within the control band defined by two preset limits.

Use level electrode NRG 26-40 in combination with level switch type NRS 2-40 or further system

components. The level data are transferred to the level switch or another system component via the

CAN data bus, adopting the CANopen protocol.

System components

NRS 2-40

Digital switching controller for level electrodes type NRG 26-40.

Functions: Four liquid levels with one switchpoint each, MAX alarm, MIN alarm, pump ON, pump OFF

with one switchpoint each, water level continuously within the predefined control band.

Data exchange: CAN bus to DIN ISO 898, using CANopen protocol.
NRR 2-40

Digital level controller for level electrodes type NRG 26-40.

Functions: Four liquid levels with one switchpoint each, MAX alarm, MIN alarm, pump ON, pump OFF

with one switchpoint each, water level continuously within the predefined control band.

Data exchange: CAN bus to DIN ISO 898, using CANopen protocol.
URB 1, URB 2

Control terminal & display unit.

Functions: Parameterization and visual display (LCD).

Data exchange: CAN bus to DIN ISO 898, using CANopen protocol.

Design

NRG 26-40:

Screwed design ¾" BSP, EN ISO 228-.

Fig. 2

Function

The principle of capacitance measurement is applied to determine the level.

The electrode rod and the vessel wall form the plates of a capacitor. If the level of the dielectric located

between these two capacitor plates changes, the current which flows through the plates changes

proportionally to the level. A dielectric is by definition an insulating substance, which excludes many

liquids such as water. In order to receive a useful measuring result the measuring rod, which is

submerged to varying depths in the liquid, must be completely insulated.

After the calibration of the zero point/measuring range (0 %/00 %) the level can be read off from a

remote display unit. The level measuring range can be changed during operation.
At regular intervals the level electrode NRG 26-40 sends a data telegram to the level switch NRS 2-40

or level controller NRR 2-40. The data transfer is effected by means of a CAN bus according to DIN ISO

898 using the CANopen protocol.