Wiring – Flowserve TRV5-40 User Manual

Page 11

Advertising
background image



Wiring

Wiring of the temperature sensor

Note that screened four-core cable, e. g. Ölflex

®

0CH, Lapp, 4 x 0.5 mm



is required for wiring

the equipment. Max. cable length between temperature sensor and temperature transmitter

TRV 5-40: 5 m.
When the equipment is open:
. Undo cable gland

I and pull the cables of the sensors through the glands.

. Strip off approx. 40 mm of cable insulation coating, remove approx. 5 mm of conductor end

insulation and disconnect the screen. Note that the screen must only be connected to the

temperature sensor.

3. Connect the sensor cables according to the wiring diagram to the terminal strip

J.

4. Fasten cable glands

I to achieve a good seal. Use sealing plugs to seal off cable glands that are

not used.

Bus line, cable length and size

Note that screened multi-core twisted-pair control cable is required for the BUS line, e. g. UNITRONIC

®

BUS CAN  x  x … mm



or RE-YCYV-fl  x  x … mm



.

Preassembled control cables (with connector and coupler) for connecting the equipment are available

as accessories.
The baud rate (data transfer rate) dictates the cable length between the bus nodes and the total power

consumption of the sensor dictates the conductor size.

When the equipment is open you can set the baud rate by using the code switch

F Fig. 3 (S 8 to 0).

The baud rate of the temperature transmitter TRV 5-40 is set at our works to 50 kBit/s (for a max.

cable length of 5 m). Reduce the baud rate if the cable length exceeds 5 m. Make sure that all

bus nodes feature the same baud rate setting.

S 8

S 9

S 10

Baud rate

Cable length

Number of pairs

and conductor size [mm

2

]

OFF

ON

OFF

250 kBit/s

125 m

 x  x 0.34

Factory setting

ON

ON

OFF

5 kBit/s

50 m

 x  x 0.5

OFF

OFF

ON

00 kBit/s

335 m

 x  x 0.75

ON

OFF

ON

50 kBit/s

500 m

on request, dependent on

bus configuration

OFF

ON

ON

0 kBit/s

000 m

ON

ON

ON

0 kBit/s

000 m

Note

The specified max. baud rates and cable lengths are based on empirical values

ascertained by GESTRA. However for some applications it might be necessary to reduce

the baud rate in order to ensure trouble-free operation.

UNITRONIC

®

is a registered trademark of LAPP Kabelwerke GmbH, Stuttgart.