Start, operation and test, Fig. 6 – Flowserve TRV5-40 User Manual

Page 17

Advertising
background image

7

Start

Apply supply voltage.

All segments and decimal

points of the displays

T

MAX

and T are flashing.

The LED displays are being tested.

Operation

Actual value T (°C) below limit

value T

MAX

(°C)

Display T

MAX

Indication of the adjusted limit

Display T

Indication of the actual value

Actual value T (°C) above limit

value T

MAX

(°C)

Display T

MAX

Indication of the adjusted limit

Display T

Indication of the actual value and triggering of

an alarm.

Control unit NRS -40. / NRS -40. opens the

output contacts after the time delay has elapsed.

Test

The pushbutton for the TRV

5-40 on the

control unit NRS

1-40.1 / NRS 1-40.2 must be

pressed and held down until

the test is finished.

Display T

An increase in temperature is simulated and

the indicated actual value rises steadily. When

the adjusted limit value is exceeded, the control

unit NRS -40. / NRS -40. opens the output

contacts after the time delay has elapsed.

Indication of an error code

When an error occurs

Display T

Display switches between indication of error

code (E xx) and actual value T. The control unit

NRS -40. / NRS 40. opens instantaneously

the output contacts and the output of terminal

7,8 is energised/de-energised in a time-

controlled manner.

Start, Operation and Test

TRV 5-40

Fig. 6

Indication of

limit value

Indication of

actual value / error code