System malfunctions, Checking installation and functions – Flowserve TRV5-40 User Manual

Page 21

Advertising
background image



System Malfunctions

– continued –

Note

The system malfunctions caused by the temperature transmitter TRV 5-40 will also

result in system malfunctions in the control units NRS -40. and NRS -40., which

means that the output contacts open instantaneously and the signal outputs are

energised/de-energised in a pulse-controlled way.
When contacting our Technical Services please state the indicated error code.

Basic values of measuring resistors

°C

0

0

0

30

40

50

60

70

80

90

00

Ω /grd

0

00.00 03.90 07.79 .67 5.54 9.40 3.4 7.07 30.89 34.70 38.50 0.385

00

38.50 4.8 46.06 49.8 53.57 57.3 6.04 64.76 68.47 7.6 75.84 0.373

00

75.84 79.5 83.7 86.8 90.46 94.08 97.70 0.30 04.88 08.46 .03 0.36

300

.03 5.58 9.3 .66 6.8 9.69 33.9 36.67 40.5 43.6 47.06 0.350

400

47.06 50.50 53.93 57.34 60.75 64.4 67.5 70.89 74.5 77.60 80.93 0.338

500

80.93 84.6 87.57 90.87 94.6 97.43 300.70 303.95 307.0 30.43 33.65 0.37

600

33.65 36.86 30.05 33.4 36.4 39.57 33.7 335.86 338.99 34.0 345. 0.35

700

345. 348.30 35.38 354.45 357.5 360.55 363.59 366.6 369.6 37.6 375.6 0.304

800

375.6 378.59 38.55 384.50 387.45 390.38

0.95

Basic values of measuring resistors according to DIN 43760 for Pt 00.

Checking the switchpoints

The switchpoints should be checked during commissioning and whenever the measuring elements of

the temperature sensors or of the temperature transmitter TRV 5-40 are being exchanged.
To check the switchpoint “MAX temperature limit (°C)” the adjusted limit value must be exceeded.
The equipment must then response as if there were an alarm situation.