Commissioning – Flowserve TRV5-40 User Manual

Page 15

Advertising
background image

5

Commissioning

– continued –

Examples of configuration settings

 Example
The following items of equipment are connected to the control unit NRS -40.:

 Level electrodes NRG x-40 for low water level LW  and 

 Level electrode NRG x-4. for high water level HW and

 Temperature transmitter TRV 5-40 for MAX temperature
As only in the temperature transmitter TRV 5-40 the limiter number can be adjusted, the control unit

NRS -40. has to be configured as follows:

Limiter

B

B

B3

B4

Function

Water level LW 1

Water level LW 2

High water HW

Temperature MAX

Set the temperature transmitter TRV 5-40 as limiter 4.

 Example
The following items of equipment are connected to the control unit NRS -40.:

 Level electrodes NRG x-40 for water level LW  and  and

 Temperature transmitter TRV 5-40 for MAX temperature

Limiter

B

B

B3

B4

Function

Water level LW 1

Water level LW 2

Temperature MAX

Set the temperature transmitter TRV 5-40 as limiter 3.

Changing system configuration

– continued –

G

Toggle switch white

Code switch

G

Limiter

Number

S

S

S3

S4

S5

S6

S7

S8

ON

ON

OFF

OFF

OFF

OFF

OFF

OFF



OFF

OFF

ON

ON

OFF

OFF

OFF

OFF



OFF

OFF

OFF

OFF

ON

ON

OFF

OFF

3

OFF

OFF

OFF

OFF

OFF

OFF

ON

ON

4

Factory setting

S9

S0

Communication with control unit

OFF

OFF

NRS -40.

ON

ON

NRS -40.