background image

4

Node ID

Should it be necessary to establish other node IDs please take the interdependence of the equipment

into consideration and assign the node ID for the individual group components according to the following

table:

Control unit

NRS 1-40.1

Sensor 1

e. g.

level electrode

NRG 1x-40

as first device

Sensor 2

e. g.

level electrode

NRG 1x-40

as second device

Sensor 3

e. g.

level electrode

NRG 1x-41.1

Sensor 4

e. g.

temperature

transmitter

TRV 5-40

X

X + 1

X + 2

X + 3

X + 4

1

2

3*

4

5

Factory setting

Reserved area

Annex

– continued –

Note

The node ID

3* for the second level electrode NRG x-40 must be set in situ because

the default factory setting is .

Changing node ID for safety part

When the housing is open:
Use a thin blade screwdriver to set switches S to S7 of the code switch

F Fig. 3 in accordance with

table “Node ID”.
Enter the adjusted node ID on the name plate.

Note

The two node IDs for the two actual value outputs (part for temperature monitoring and

control) are linked with the node ID of the safety part and cannot be adjusted. For more

information see the installation manual of the control unit TRS 5-40.

Attention

Do not use a node ID for more than one item of equipment in the CAN bus system.
The node ID 0 is not permissible.