After applying mains voltage LEDs and do not light up

Fault:

The mains voltage is not applied across the equipment.

Remedy: Apply mains voltage. Check installation of the 19" slide-in unit.

Fault:

The internal fuse is defective.

Remedy: Remove the 19" slide-in unit and replace the internal fuse.

Incorrect measuring current between electrode terminal 2 and NRS terminal
5 or A22 defective

Fault:

The level transmitter NRGT 26-1s is defective.

Remedy: Check level transmitter (see installation instructions NRGT 26-1s).

Level switch does not work properly despite correct measuring current

Fault:

The level switch NRS 2-3 is defective.

Remedy: Replace level switch.

Annex

Fault finding list for troubleshooting

Warning

The terminal strip of the NRS 2-3 is live during operation. This presents the
danger of electric shock.
Cut off power supply before inserting or removing the 19" slide-in unit and
before carrying out any installation or maintenance work.