E4: cpu frequency select, E8: phase clock lines output enable, E9: servo clock lines output enable – Delta Tau PMAC2A-PC/104 User Manual

Page 48: E10 – e12: power-up state jumpers

Advertising
background image

PMAC2A PC104 Hardware Reference Manual

Base Board E-Point Jumper Descriptions

42

E4: CPU Frequency Select

E Point and

Physical Layout

Location Description

Default

E4

C4

Remove jumper for 40 MHz operation (E2
OFF also) or for 60 MHz operation (E4 ON).

Jump pin 1 to 2 for 80 MHz operation (E2
OFF).

No jumper installed
(standard or Option 5EF)

Jumper installed (Option
5CF)

E8: Phase Clock Lines Output Enable

E Point and

Physical Layout

Location Description

Default

E8

B1

Jump pin 1 to 2 to enable the PHASE clock
line on the J8 connector, allowing
synchronization with another PMAC.

Remove jumper to disable the PHASE clock
line on the J8 connector.

No Jumper

E9: Servo Clock Lines Output Enable

E Point and

Physical Layout

Location Description

Default

E9

B1

Jump pin 1 to 2 to enable the SERVO clock
line on the J8 connector, allowing
synchronization with another PMAC.

Remove jumper to disable the SERVO clock
line on the J8 connector.

No Jumper

E10 – E12: Power-Up State Jumpers

E Point and

Physical Layout

Location Description

Default

E10

E12

E5 Remove

jumper

E10;

Jump E11;
Jump E12;

To read flash IC on power-up/reset
Other combinations are for factory use only;
the board will not operate in any other
configuration.

No E10 jumper installed;

Jump E11 and E12

Advertising