Table 1: IPS Beacon factory default settings

Parameter

Default setting

(metric units)

Default setting

(US units)

X-axis vibration
alarm level

9.4 mm/s

0.38 in./sec

Y-axis vibration
alarm level

9.4 mm/s

0.38 in./sec

Z-axis vibration
alarm level

9.4 mm/s

0.38 in./sec

Temperature
alarm level

85 °C

185 °F

Vibration
readings type

RMS

Data log interval

5 minutes

Average number
of readings for
alarm limit

2 readings

See section 5, Custom configuration programming, to
change any of the above settings.

3.2 Alarm mode

By default the IPS Beacon enters alarm mode when
the average of two readings, of either vibration or
temperature, exceed the predefined alarm limits.
Alarm mode is indicated with a flashing red light. The
user should do a physical detailed analysis of the
equipment being monitored when the alarm is
activated. (See Table 2: LED indicator lights
description with PUM
installed.
)

Table 2: LED indicator lights description with
PUM installed

LED

State

Description

GREEN

3 quick
flashes

Indicates that IPS Beacon has been
powered on

GREEN

Flash every
5 seconds

Normal operation

– vibration and

temperature are within acceptable limits

RED

Flash every
5 seconds

Current alarm

– one of the

measurements has exceeded its alarm
limit and has not returned within the
acceptable range

RED &
GREEN

Flash every
5 seconds

Alarm

– one of the measurements

previously exceeded its alarm limit, but has
now returned within the acceptable range

3.3 Performance and operation limits

This product has been selected to meet the
specification of your purchase order.

The following data is included as additional
information to help with your installation. This is
typical information and if required, a definitive
statement for your application can be obtained from
Flowserve.

3.3.1 IPS Beacon nomenclature

Table 3: IPS Beacon nomenclature

Flowserve
item code

Generic
designation

Specifications

Material

9050

VB-105

IPS Beacon compact
monitor

316L SS

Fastener

M6 (¼ - 28)

18-8

This product must not be operated

beyond the parameters specified for the application.
If there is any doubt as to the suitability of the product
for the application intended, contact the manufacturer
for advice.

IPS Beacon material compatibility is

the responsibility of the end user.

3.3.2 Sensor specifications

Table 4: IPS Beacon and sensor specifications

IPS Beacon components

Channels (internal)

1-battery voltage, 1-onboard
temperature, 3-vibration (X, Y, Z)

Measurement rates

1 to 60 minutes

Ambient temperature

-40 °C (-40 °F) to +85 °C (185 °F)

Power requirement

3.6 VDC internal battery pack

Outer shell

316LSS with Borosilicate glass lens

Mounting

M6 (¼ x 28) stud mount

IPS Beacon sensor components

Variable

Limit

Vibration (velocity)

Tri axis 0-25 mm/s (0

– 1 IPS) peak or

RMS. Accuracy +/- 10 % full scale

Surface temperature (T

s

)

measurement range

-40 °C (-

40 °F) ≤ T

s

≤ +93.33 °C (200

°F). Accuracy +/-2.8 °C (5 °F)

IPS Beacon

operational state

Battery life

Normal operating and
environmental conditions

4 years with 5 minute sampling

Alarm mode

4 years

Note: Measurement accuracy for surface temperature (range -40 to
93.33 °C) and vibration (range 0 to 25 mm/s) is absolute accuracy of
the measurement relative to a known, calibrated device. Values
shown represent the expected performance operating under steady
state conditions at 23 °C (73 °F) with no external interferences.
Note: The IPS Beacon temperature measurement is optimized for
surface temperature readings of an operating bearing housing.


3.3.3 Battery

The IPS Beacon battery is not

replaceable.
You must replace the entire unit once the battery runs
out of power. The battery life is not covered as part
of the standard device warranty. Table 4 shows the
average battery life under normal and alarm mode
operating conditions.