Troubleshooting
(continued)
ADD IG -- (at search mode „ADD IG“)
Cause:
Power supply to Fronius IG / IG Plus has been lost on the DC side
Remedy:
Check power supply of Fronius IG / IG Plus on the DC side
Cause:
Old Firmware version Fronius IG / IG Plus
Remedy:
Update Firmware version
ERROR IG XX
in „ADD IG“ search mode
Cause:
Fronius IG / IG Plus address number is greater than 15
Remedy:
Check number on the inverter and correct it if necessary.
ERROR BATT
Power supply connected, battery charging
Cause:
Wrong or faulty batteries installed.
Remedy:
Check batteries
FULL LIST
in „ADD IG“ search mode
Cause:
There are already 15 Fronius inverter in the system.
No communication is possible between the personal display and the inverter
Cause:
Only one personal display can ever communicate with the inverter in
the system.
Remedy:
If the personal display is replaced with a new one, then all the
Fronius IG / IG Plus in the system should be deleted from the perso-
nal display’s configuration (see „The Setup menu“, section „DEL
IG“).
NOTE! If the inverters in the system have not been deleted from the configurati-
on of the personal display and if the personal display used previously is no
longer available (because of damage, for instance), then the display card in the
Fronius IG / IG Plus must be reset.
Resetting the display card on the Fronius IG / IG Plus:
1.
Open the setup menu and choose „DatCom“
2.
Use arrow keys to move to the „PDCD RST“ menu item
3.
Press the Enter key to reset the display card