Operation, Maintenance, Functional operation – GAI-Tronics 12598-002 Redundant 5 V DC Module User Manual

Page 3

Advertising
background image

Pub. 42004-405A

Model 12598-002 Redundant 5 V DC Module

Page: 3 of 5

\\s_eng\gtcproddocs\standard ioms - current release\42004 instr. manuals\42004-405a.doc
01/08

Operation

After successful installation and testing, the Model 12598-002 Module requires no operator intervention.

Functional Operation

The Model 12598-002 Redundant 5 V DC Module operates with two 5 V dc power supplies. When 5 V
dc power is applied to the PS1

IN and PS2

IN terminals of the module, relays K1 and K2 become active.

Output voltage at the DC

OUT terminals will be approximately 4.1 V to 4.4 V dc, which is due to a

voltage drop of approx. 0.6 V to 0.9 V depending on the load current through CR1 and CR2. Thus, as
load current increases through the diodes, the voltage drop across each diode increases toward the
maximum value of 0.9 V. The power supplies should be adjusted above 5 V to compensate for the
voltage drop.

Also, since CR1 or CR2 have a slightly different voltage drops (or turn-on thresholds), either of the
connected power supplies (at PS1

IN or PS2

IN) may initially supply power to load.

Maintenance

The Model 12598-002 Redundant 5 V DC Module does not contain any user serviceable parts. Do not
attempt to make any repairs to the module.

If the module requires service, contact your Regional Service Center for a return authorization number
(RA#). The module should be shipped prepaid to GAI-Tronics with a return authorization number and a
purchase order number. If the module is under warranty, repairs or a replacement will be made in
accordance with GAI-Tronics’ warranty policy. Please include a written explanation of all defects to
assist our technicians in their troubleshooting efforts.

Call 800-492-1212 inside the USA or 610-777-1374 outside the USA for help identifying the Regional
Service Center closest to you.

Advertising