Model 13118-009 TVP Barrier Assembly

Page: 3 of 4

\\s_eng\gtcproddocs\standard ioms - current release\42004 instr. manuals\42004-678l2a.doc

10/02

Pin No. Function

Remarks

16

CLS-

This terminal is used with CLS+ when dry contact All-Call control is
employed at field stations via a separate pair of wires.

17 EGND

Earth

ground

18 EGND

Earth

ground


N

OTE

: Terminal Blocks JTB2 and JTB3 are for internal cabinet wiring only. Do not connect any field

cables to either of these terminal blocks.

Installation

CAUTION

Safety Note: If GAI-Tronics Page/Party

®

cable is used, ensure the ac power conductors are disconnected

from any power source during the installation.

1. Snap the Modular TVP Barrier assembly onto one of the vertical DIN mounting rails located in the

rear of the cabinet.

2. Connect the appropriate Page/Party

®

cable to modular terminal block JTB1 per table 1 using the

mating plug provided.

3. Attach the appropriate ribbon cable to the DB-25 connector (J1).

4. Attach a ground wire to JTB1-17 or JTB1-18.

5. If this module is replacing a damaged module, re-connect (plug-in) any pre-wired harnesses to/from

other modules at JTB2 and JTB3.

6. Check and/or set positioning of the party line jumper clips J2 through J7 per the following chart:

Jumper Clip

Pair

Party Line Position 1 Position 2

J2/J3 3

Connected

Isolated

J4/J5 4

Connected

Isolated

J6/J7 5

Connected

Isolated


*N

OTE

: All jumper clips are factory set to position 1. Setting any jumper clip pair to the “Isolated”

position automatically applies 33-ohm line balancing to the designated line.

Operation

None.

Software Configuration

None.