Changing to a 69257-101 API from a previous version

N

OTES

:

1. The 69257-101 API is not electrically compatible with its predecessors. If further information on the

differences is needed, please contact the GAI-Tronics Field Service Department at 800-492-1212.

2. When upgrading to a 69257-101 API, the following four upgrades are required:

Any 69266-001 or 69320-001 VNAs must be upgraded to the 69320-101 VNA.

Any 69257-003, 69257-002, or 69257-001 APIs must be upgraded to the 69257-101 API.

Any 69510-001, 69215-003, 69215-002, or 69215-001 backplane termination boards must be
upgraded to the 69510-101 Termination board. Two of these boards are required per card rack.

The upgraded cards must be installed in the proper backplane slot.

This task involves moving the

card and the associated ribbon cable at the rear of the card rack assembly.

Revisions of the API prior to the 69257-101 revision (the –003, -002, and –001 revisions) used a different
switch and jumper collection than the 69257-101 revision. The following text states how to convert the
previous revisions’ switch and jumper settings into the 69257-101 switch and jumper settings.

The 2xx/3xx Address header (P2) and shorting clip should be set to the 2xx position if W1 is inserted in the
API being replaced; otherwise, set to the 3xx position.

The Board Address rotary switch (SW4) is present on all versions of the API.

The Board Identification rotary switch (SW3) is present on all versions of the API.

The Clock Master/Clock Slave header (P3) and shorting clip should be set to M

ASTER

if the three shorting

clips were installed on header J8 (labeled M

ASTER

). Otherwise, set the jumper to S

LAVE

.

N

OTE

: The 69257-001 API has two shorting clips instead of three.

The ST-Bus Stream In rotary switch (SW2) should be set to “F”.

The ST-Bus Stream Out rotary switch (SW1) should be set to “F”.

If a 69320-101 Voice Network Adapter is installed in the system, then the P12 and P13 shorting clips
should be in the 1-2 position (ISOLATED). Otherwise, the P12 and P13 shorting clips should be in the 2-3
position (CONNECTED).

API-to-access panel data line isolation headers (P5, P7, P8, P9, P11, P14, P15, and P16) and shorting clips
should be in the 1-2 position (GROUNDED). However, if this setting results in a ground loop between the
API and a particular access panel, then set the shorting clip associated with that access panel to the 2-3
position (FLOATING).