Venting installation, Continued – Desa SBVBN(C) User Manual

Page 11

Advertising
background image

106828-01C

For more information, visit www.desatech.com

For more information, visit www.desatech.com

11

11

VENTING INSTALLATION

Continued

CHECKING VENT CAPACITY

Complete all gas piping, electrical, and vent connections. After adjust-
ing the burner system and lighting the main burners, allow a couple of
minutes for warm-up. Hold a lighted match just under the rim of the
draft hood relief opening. Proper venting will draw the flame toward or
into the draft hood. Improper venting, indicated by escape or spillage of
burned gas, will cause match to flicker or go out. Smoke from a cigarette
will also be pulled into the draft hood if the vent is drawing properly.

Figure 25 - Test for Proper Venting

CHIMNEYS

• Complete familiarity with chimney condition, height, size, clear-

ance to combustibles and other factors is essential.

NOTICE: Consult the authority having jurisdiction
in your area regarding masonry chimney venting
applications.

NOTICE: A complete chimney inspection by a quali-
fied person should be performed.

• Appliances using B-vent connectors to vent into a masonry or

factory-built chimney should not exceed 1

1

/

2

feet in length for

every inch of connector diameter (3" vent connector has a maxi-
mum 4

1

/

2

foot length; 5" connector has maximum 7

1

/

2

foot length).

• Oversized chimneys should be relined with appropriate listed

relining systems.

• Cleanout access may be required.

NOTICE: Consult the authority having jurisdiction in
your area regarding listed chimney liner venting
applications.

WARNING: Operation of improperly installed and

maintained venting system could result in serious
injury, property damage, or loss of life.

RELINING SYSTEMS

• Suitability and approval of relining materials should be determined.

• Condition, size, height, and termination of the chimney to

be relined must be determined.

• No substitution of components should be made.

• Joints and connectors should be made according to

manufacturer’s instructions.

Figure 26 - Straight
Installation into Masonry
Chimney

Figure 27 - Typical Straight
Installation with Listed Chimney
Liner

HIGH ALTITUDE INSTALLATION

Your DESA B-vent burner system has been AGA tested and ap-
proved for elevations from 0-2000 feet and CGA certified for eleva-
tions from 0-4500 feet.

When installing this burner system at an elevation above 2000 feet (in
the USA), you may need to decrease the input rating by changing the
existing burner orifice to a smaller size. Reduce input 4% for each
1000 feet above sea level. Check with your local gas company for
proper orifice size identification and proper orifice for your location.

When installing this stove and burner system at an elevation above
4500 feet (in Canada), check with local authorities.

For assistance with any high altitude installation contact DESA’s
Technical Service Department at 1-866-672-6040.

VENTING INSTALLATION

Checking Vent Capacity

Chimneys

Relining Systems

High Altitude Installation