Installing, Warning, Notice – Desa FB32C User Manual

Page 10: Caution

Advertising
background image

10

103296

INSTALLATION CLEARANCES

WARNING ICON

G 001

WARNING

Maintain the minimum clearances. If you can, provide greater
clearances from floor, ceiling, and adjoining wall.

Carefully follow the instructions below. This will ensure safe installation.

Minimum Wall and Ceiling Clearances (see Figure 6, page 11)

A. Clearances from the side of the firebox opening to any combustible wall should not

be less than 16 inches for a cabinet mantel or 12 inches for a corner installation.

B. Clearances from the top of the firebox opening to the ceiling should not be less

than 42 inches.

INSTALLING

NOTICE

A qualified service person must install firebox. Follow all local
codes.

WARNING ICON

G 001

WARNING

Never install the firebox

• in a bedroom or bathroom
• in a recreational vehicle
• where curtains, furniture, clothing, or other flammable

objects are less than 36 inches from the front, top, or sides
of the firebox

• in high traffic areas
• in windy or drafty areas

WARNING ICON

G 001

CAUTION

Log heaters installed in this firebox create warm air currents.
These currents move heat to wall surfaces next to firebox. Install-
ing firebox next to vinyl or cloth wall coverings or operating
firebox where impurities in the air (such as tobacco smoke) exist,
may discolor walls.

IMPORTANT:

Vent-free gas log heaters add moisture to the air. Although this is

beneficial, installing firebox in rooms without enough ventilation air may cause
mildew to form from too much moisture. See Air for Combustion and Ventilation,
pages 6 through 9.

IMPORTANT:

Make sure the firebox is level. If firebox is not level, log set will not

work properly.