Fresh air for combustion and ventilation, Warning – Desa CGN10L User Manual

Page 7

Advertising
background image

7

103546

FRESH AIR

FOR

COMBUSTION

AND

VENTILATION

Continued

Or

Remove

Door into

Adjoining

Room,

Option 3

Ventilation Grills

Into Adjoining Room,

Option 2

12"

12"

Ventilation

Grills

into Adjoining

Room,

Option 1

WARNING ICON

G 001

WARNING

If the area in which the heater may be operated is smaller than
that defined as an unconfined space, provide adequate combus-
tion and ventilation air by one of the methods described in the
National Fuel Gas Code, ANSI Z223.1, 1992, Section 5.3 or appli-
cable local codes.

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining unconfined space. When ventilating to
an adjoining unconfined space, you must provide two permanent openings: one within
12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces
(see options 1 and 2, Figure 2). You can also remove door into adjoining room (see
option 3, Figure 2). Follow the National Fuel Gas Code NFPA 54/ANSI Z223.1,
Section 5.3, Air for Combustion and Ventilation
for required size of ventilation grills
or ducts.

WARNING ICON

G 001

WARNING

Rework worksheet, adding the space of the adjoining unconfined
space. The combined spaces must have enough fresh air to supply all
appliances in both spaces.

Figure 2 - Ventilation Air from Inside Building

Continued