Medium-large size system, By-pass on top of risers 1 1, Chilled water system, central by-pass – Infloor Pressure Differential by Pass 31075, 31076, 31077 User Manual

Page 4: Chiller, Infloor sales and service, Caleffi

Advertising
background image

Medium-large size system

by-pass on top of risers

1

1

mH2O 6

mH2O 6

RT

RT

RT

RT

RT

RT

RT

RT

V

Chilled water system, central by-pass

RT

RT

RT

RT

CHILLER

SPECIFICATION SUMMARIES


Differential pressure by-pass valve. Threaded connections 3/4” MNPT x 3/4” MNPT outlet, 3/4" Sweat x 3/4" Sweat outlet
1” FNPT x 1” MNPT outlet, 1” FNPT x 1” sweat outlet, 1 1/4” FNPT x 1 1/4” MNPT outlet and 1 1/4” FNPT + 1 1/4” sweat
outlet. Brass body. Brass valve plug. EPDM valve plug gasket. EPDM O-Ring seals. Asbestos free NBR union seals. ABS
control knob. Stainless steel spring. Medium: water, glycol solutions. Maximum percentage of glycol 30%. Temperature
range 32–230°F (0–110°C). Maximum working pressure 150 psi (10 bar). Setting range is 1 - 6 m w.g. (2–10 psi) and 3/4”
flow up to 9 gpm (1” flow up to 40 gpm and 1 1/4” flow up to 45 gpm).

We reserve the right to change our products and their relevant technical data, contained in this publication, at any time and without prior notice.

CALEFFI

Infloor Sales and Service

P.O. Box 4945, 503 Gregg Drive, Buena Vista CO 81211

Tel: 719.395.3400 / Fax: 719.395.3400 /

www.Infloor.com

Advertising