Installation, Mantel clearances, Continued – Desa CCL3018PTA User Manual

Page 10

Advertising
background image

www.desatech.com

113097-01C

10

If Using Mantel

You must have noncombustible material(s) above

the fireplace opening. Noncombustible materials

(such as slate, marble, tile, etc.) must be at least

1/2 inch thick. With sheet metal, you must have

noncombustible material behind it. Noncombus-

tible material must extend at least 8" up (for all

models). If noncombustible material is less than

12", you must install the fireplace hood accessory

(24" and 30" models only). Even if noncombus-

tible material is more than 12", you may need the

hood accessory to deflect heat away from your

mantel shelf. See Figure 5 and 6 and Figure 7 on

page 11 for minimum clearances.

MANTEL CLEARANCES

In addition to meeting noncombustible material

clearances, you must also meet required clearances

between fireplace opening and mantel shelf. If

you do not meet the clearances in Figure 6 you

will need a hood.
Determining Minimum Mantel Clearance
If you meet minimum clearance between mantel

shelf and top of fireplace opening, a hood is not

required (see Figure 6).
Determining Minimum Mantel Clearance
When Using a Hood
If minimum clearances in Figure 6 are not met, you

must have a hood. When using a hood there are

still certain minimum mantel clearances required.

Follow minimum clearances shown in Figure 7,

page 11 when using hood.

NOTICE: Surface temperatures

of adjacent walls and mantels be-

come hot during operation. Walls

and mantels above the firebox

may become hot to the touch.

If installed properly, these tem-

peratures meet the requirement

of the national product standard.

Follow all minimum clearances

shown in this manual.

INSTALLATION

Continued

Noncombustible Requirements for
Material

Safe Installation

Distance (A)
12" or more

Noncombustible material

okay.

Between 8"

24", 30" or 36" Models:

and 12"

Install fireplace hood

accessory (GA6050,

GA6052 or GA6053 see

Accessories, page 38).

18" Model: Noncombus-

tible material okay.

Less than 8"

Noncombustible material

must be extended to at

least 8". See Between 8"

and 12", above. If you

cannot extend material,

you must operate heater

with flue damper open.

IMPORTANT:

If you cannot meet these minimum

clearances, you must operate heater with chimney

flue damper open. Go to Installing Damper Clamp

Accessory for Vented Operation, page 11.

Heat Resistant
Material

(A)

Figure 5 - Heat Resistant Material (Slate,

Marble, Tile, etc.) Above Fireplace

Figure 6 - Minimum Mantel Clearances

Without Using Hood

Minimum

Noncombustible

Material

Minimum

Noncombustible

Material Height

Distances to

Underside of

Mantel

Top of Fireplace

Opening

Underside

of Mantel

Shelf

Mantel Shelf

12"
8"

(A)

18"
8"

20"
14"

22"
17"

24"
20"

All minimum

distances

are in inches

Log Set
24"/30"

Models
18" Model

2

1/2

"

6"

8"

10"

Advertising
This manual is related to the following products: