INSTALLATION

Continued

CAUTION: Make sure exter-

nal regulator has been installed

between propane/LP supply and

heater. See guidelines under Con-

necting to Gas Supply, page 13.

PRESSURE TESTING GAS SUPPLY
PIPING SYSTEM
Test Pressures In Excess Of 1/2 PSIG
(3.5 kPa)
1. Disconnect appliance with its appliance main

gas valve (control valve) and equipment

shutoff valve from gas supply piping system.

Pressures in excess of 1/2 psig will damage

heater regulator.

2. Cap off open end of gas pipe where equipment

shutoff valve was connected.

3. Pressurize supply piping by either opening

propane/LP supply tank valve for propane/LP

gas or opening main gas valve located on or

near gas meter for natural gas or using com-

pressed air.

4. Check all joints of gas supply piping system.

Apply a noncorrosive leak detection fluid to

all joints. Bubbles forming show a leak.

5. Correct all leaks at once.

6. Reconnect heater and equipment shutoff valve

to gas supply. Check reconnected fittings for

leaks.

Test Pressures Equal To or Less Than
1/2 PSIG (3.5 kPa)
1. Close equipment shutoff valve (see Figure 16).

2. Pressurize supply piping system by either

opening propane/LP supply tank valve for

propane/LP gas or opening main gas valve

located on or near gas meter for natural gas

or using compressed air.

3. Check all joints from gas meter to equipment

shutoff valve for natural gas or propane/LP

supply to equipment shutoff valve for pro-

pane/LP (see Figures 17 and 18). Apply

noncorrosive leak detection fluid to all joints.

Bubbles forming show a leak.

4. Correct all leaks at once.
PRESSURE TESTING HEATER GAS
CONNECTIONS
1. Open equipment shutoff valve (see Figure 16).

2. Open main gas valve located on or near gas

meter for natural gas or open propane/LP

supply tank valve.

3. Make sure control knob of heater is in the OFF

position.

4. Check all joints from equipment shutoff valve

to thermostat gas valve (Thermostat-Con-

trolled Models) or to control valve (Manu-

ally-Controlled Models) (see Figures 17 and

18). Apply noncorrosive leak detection fluid

to all joints. Bubbles forming show a leak.

5. Correct all leaks at once.
6. Light heater (see Operating Heater, page

19 [manually-controlled models] or page 21

[thermostatically-controlled models]). Check

all other internal joints for leaks.

7. Turn off heater (see To Turn Off Gas to Appli-

ance, page 20 [manually-controlled models] or

page 22 [thermostatically-controlled models]).

Figure 16 - Equipment Shutoff Valve

Figure 17 - Checking Gas Joints

(Propane/LP Gas Models)

Equipment
Shutoff Valve

Propane/LP
Supply Tank

Thermostat Gas Valve or
Control Valve Location

Figure 18 - Checking Gas Joints (Natural

Gas Models)

Gas Meter

Equipment
Shutoff Valve

Thermostat Gas Valve or
Control Valve Location

Equipment
Shutoff
Valve

Open

Closed