For propane/LP units, the installer must supply

an external regulator. The external regulator will

reduce incoming gas pressure. You must reduce

incoming gas pressure to between 11 and 14 inches

of water. If you do not reduce incoming gas pres-

sure, heater regulator damage could occur. Install

external regulator with the vent pointing down

as shown in Figure 14. Pointing the vent down

protects it from freezing rain or sleet.

CAUTION: Use only new,

black iron or steel pipe. Inter-

nally-tinned copper tubing may

be used in certain areas. Check

your local codes. Use pipe of

1/2" diameter or greater to allow

proper gas volume to heater. If

pipe is too small, undue loss of

volume will occur.

Installation must include an equipment shutoff

valve, union and plugged 1/8" NPT tap. Locate NPT

tap within reach for test gauge hook up. NPT tap

must be upstream from heater (see Figure 15).
IMPORTANT:

Install equipment valve in an acces-

sible location. The equipment shutoff valve is for

turning on or shutting off the gas to the appliance.
Check your building codes for any special re-

quirements for locating equipment shutoff valve

to fireplaces.
Apply pipe joint sealant lightly to male NPT

threads. This will prevent excess sealant from

going into pipe. Excess sealant in pipe could result

in clogged heater valves.

WARNING: Use pipe joint

sealant that is resistant to liquid

petroleum (LP) gas.

We recommend that you install a sediment trap in

supply line as shown in Figure 15. Locate sediment

trap where it is within reach for cleaning. Install

in piping system between fuel supply and heater.

Locate sediment trap where trapped matter is not

likely to freeze. A sediment trap traps moisture and

contaminants. This keeps them from going into

heater controls. If sediment trap is not installed or

is installed wrong, heater may not run properly.

CAUTION: Avoid damage

to regulator. Hold gas regulator

with wrench when connecting it

to gas piping and/or fittings.

INSTALLATION

Continued

Figure 15 - Gas Connection

* Purchase the optional CSA design-certified

equipment shutoff valve from your dealer. See

Accessories, page 38.
** Minimum inlet pressure for purpose of input

adjustment.

3" Minimum

Sediment Trap

Gas
Regulator

CSA Design-
Certified Equipment
Shutoff Valve With
1/8" NPT Tap*

Approved Flexible
Gas Hose (if allowed
by local codes)

Tee

Pipe Cap

Joint Nipple

Figure 14 - External Regulator With Vent

Pointing Down

Propane/LP
Supply Tank

External
Regulator

Vent
Pointing
Down

PROPANE/LP
From External
Regulator (11" W.C.**
to 14" W.C. Pressure)
NATURAL
From Gas Meter
(5" W.C.** to
10.5" W.C.
Pressure)

CHECKING GAS CONNECTIONS

WARNING: Test all gas pip-

ing and connections, internal

and external to unit, for leaks

after installing or servicing. Cor-

rect all leaks at once.

WARNING: Never use an open

flame to check for a leak. Apply a

noncorrosive leak detection fluid

to all joints. Bubbles forming show

a leak. Correct all leaks at once.