Water pipe connection, Installation (cont.) – MovinCool CMW30 User Manual
Page 16

16
INSTALLATION (cont.)
Water Pipe Connection
WARNING: Before wiring the unit, connect the water line to the unit.
To avoid electrical shock, make sure that there is no water splashed
onto the electrical box.
CMW30 unit is equipped with two female 3/4 inch NPT (National Pipe Thread)
connectors for water connections. Two water pipes with 3/4 inch NPT Male
connectors and proper insulators are required for field installation.
Connecting Water Pipes
1. Remove the caps from the NPT connectors on the rear side of the unit.
Note: Small residues of water may drip from the NPT connectors when the caps
are first removed.
2. Apply teflon tape to the NPT male connectors.
3. Connect the threaded water pipes or pipes with the NPT male connectors to
the NPT female connectors on the unit. Hold the wrench A tightly so that the
pipe on the unit is not deformed, then tighten the connector with the wrench B.
CAUTION: Use proper size wrenches.
WRENCH A
WRENCH B
ILL00332-00