Troubleshooting – MovinCool CMW30 User Manual

Page 52

Advertising
background image

52

TROUBLESHOOTING

Check the following conditions before calling your MovinCool reseller or a qualified

technician.

If conditions persist after the above remedies have been performed, turn off the

unit, disconnect the power, and contact your MovinCool reseller or a qualified

technician.

Condition

Check Area

Possible Cause

Remedy

Unit

operates.

Insufficient

air volume

Filter

Air filter is clogged.

Clean or replace air filter.

Duct

Leak or clog on the

duct connection

Repair duct connection.

Using longer duct

length or smaller

duct diameter than

recommended.

Change the duct to

proper size.

Fan

Fan is locked.

Remove any foreign

object causing fan lock.

Unit

does not

operate.

LCD

display

turns off.

1. Voltage

Power failure

Repair power supply.

Turn the circuit breaker

on.

2. Ground fault

breaker trip

Ground fault or

defective ground

fault.

Repair ground fault

section.

Reset or repair breaker.

3. Fuse

Fuse is blown.

Replace fuse on the

relay board.

4. Wall mounted

controller/

millivolt wall

thermostat

Incorrect connection Connect the wires

correctly. (See “Supplied

Wall Mounted Controller

Connection” on page 26

to 31 or “Field-Supplied

Millivolt Wall Thermostat

Connection” on page 31

to 33.)

DIP switch setting is

incorrect.

Correct DIP switch

setting. (See “DIP Switch

Configuration and

Setting” on page 24.)

5. Stop switch

Stop switch is in the

STOP position.

Turn the stop switch to

the OPERATE position.