Figure 23 - Equipment Shutoff Valve

Open

Closed

Equipment
Shutoff
Valve

Figure 25 - Checking Gas Joints Natural

Gas (Shown with Optional Mantel)

Gas Meter

Equipment
Shutoff Valve

INSTALLATION

Continued

3. Check all gas connections for leaks. See

Checking Gas Connections.

4. Feed flexible gas line into fireplace base area.

Make sure the entire flexible gas line is in

fireplace mantel base area.

CAUTION: Avoid damage to

regulator. Hold gas regulator

with wrench when connecting it

to gas piping and/or fittings.

CHECKING GAS CONNECTIONS

WARNING: Test all gas piping

and connections, internal and

external to unit, for leaks after

installing or servicing. Correct

all leaks at once.

WARNING: Never use an

open flame to check for a leak.

Apply a noncorrosive leak detec-

tion fluid to all joints. Bubbles

forming show a leak. Correct all

leaks at once.

CAUTION: Make sure exter-

nal regulator has been installed

between propane/LP supply and

heater. See guidelines under Con-

necting to Gas Supply, page 15.

PRESSURE TESTING GAS SUPPLY
PIPING SYSTEM
Test Pressures In Excess Of 1/2 PSIG
(3.5 kPa)
1. Disconnect appliance with its appliance main

gas valve (control valve) and equipment

shutoff valve from gas supply piping system.

Pressures in excess of 1/2 psig will damage

heater regulator.

2. Cap off open end of gas pipe where equipment

shutoff valve was connected.

3. Pressurize supply piping system by either

opening propane/LP supply tank valve for

propane/LP gas or opening main gas valve

located on or near gas meter for natural gas

or using compressed air.

4. Check all joints of gas supply piping system.

Apply noncorrosive leak detection fluid to all

joints. Bubbles forming show a leak.

5. Correct all leaks at once.
6. Reconnect heater and equipment shutoff valve to

gas supply. Check reconnected fittings for leaks.

Test Pressures Equal To or Less Than
1/2 PSIG (3.5 kPa)
1. Close equipment shutoff valve (see Figure 23).
2. Pressurize supply piping system by either

opening propane/LP supply tank valve for

propane/LP gas or opening main gas valve

located on or near gas meter for natural gas

or using compressed air.

3. Check all joints from gas meter to equipment

shutoff valve for natural gas or propane/LP sup-

ply to equipment shutoff valve for propane/LP

(see Figures 24 and 25). Apply noncorrosive

leak detection fluid to all joints. Bubbles form-

ing show a leak.

4. Correct all leaks at once.

Figure 24 - Checking Gas Joints Propane/LP

Gas (Shown with Optional Mantel)

Equipment Shutoff Valve

Propane/LP
Supply Tank