Repair Section
60
Troubleshooting of Insufficient Cooling or Heating - Table 1
Condition
Check Area
Possible Cause
Remedy
Insufficient Cooling
or Heating
Air volume 
normal
Compressor 
operates.
Usage conditions
(high/low temperature)
Operates near minimum or 
maximum of operation 
range.
Review the installation 
place.
Dirt in the indoor or outdoor 
heat exchanger
Insufficient heat exchange
Clean the heat 
exchangers.
Frost in the refrigeration 
system
Clogging at the frost section
Service the refrigeration 
system.
No temperature difference 
between indoor and outdoor 
heat exchangers
Insufficient refrigerant
Check the leaking part, 
then repair and charge 
the correct amount of 
refrigerant.
Compressor 
does not
 operate.
Voltage
Low voltage
Repair the power supply.
Compressor relay on the
relay board
Open circuit or insufficient 
contact surface area
Replace the relay board.
Capacitor for compressor 
motor
Capacitor malfunction
Replace the capacitor.
Compressor coil resistance
(0 ohm or 
∞ ohm)
Short or open circuit
Replace the compressor.
(In case of short, check
the compressor relay.)
Abnormal
air volume
No air
Fan on-off relay on the relay 
board
Open circuit or insufficient 
contact surface area
Replace the relay board.
Coil resistance of indoor or 
outdoor fan motor
(0 ohm or 
∞ ohm)
Short or open circuit
Replace the fan motor.
Insufficient
 air volume
Air filter
Clogged air filter
Clean the air filter.
Indoor or outdoor heat 
exchanger
Clogged indoor or outdoor 
heat exchanger
Clean the indoor or 
outdoor heat exchanger.
Crushed fins
Repair or replace the 
heat exchanger.
Duct connection state
Improper connection
Repair duct connection.
Indoor or outdoor fan motor
Abnormal rotation
Replace the fan motor.
Fan speed change relay on the 
relay board
Open circuit or insufficient 
contact surface area
Replace the relay board.