MovinCool Climate Pro 18 Service Manual User Manual
Page 66
 
Repair Section
66
Troubleshooting of Unit does not operate - Table 5
Condition
Check Area/Diagnostic
Code
Possible Cause
Remedy
Unit does 
not operate.
LCD 
displays 
self-
diagnostic 
codes.
E4
Loose CTS2 thermistor
connection
Reconnect the CTS2 
thermistor and check 
connection.
Defective CTS2 thermistor 
(short or open)
Replace the CTS2 
thermistor.
E5
Loose CTS3 thermistor
connection
Reconnect the CTS3 
thermistor and check 
connection.
Defective CTS3 thermistor 
(short or open)
Replace the CTS3 
thermistor.
LCD 
displays 
notification.
OUTSIDE OPERATING 
RANGE
Unit is operating outside 
operating range.
Check product specification 
for temperature operating 
range.
Press any key to exit.
DEFROST
Unit is under defrost control. Wait until defrost control is
completed.
KEY LOCKED
Buttons on the control panel 
are locked.
Press and hold MENU/ESC 
button for 5 seconds to 
unlock.
EXTERNAL THERMOSTAT 
ACTIVATED
Status is changed to control 
by an external thermostat.
Operate the unit by an 
external thermostat.
LCD shows 
normal, but 
the unit does 
not start.
Set point temperature
Room temperature
reached the set point
temperature and the unit 
operation stopped.
Adjust the set point 
temperature.
Unit stops
immediately
after 
starting.
LCD 
displays
normally.
Fan on-off relay on the relay 
board
Open circuit or insufficient 
contact surface area
Replace the relay board.
Fan speed change relay on 
the relay board
Open circuit or insufficient 
contact surface area
Replace the relay board.
Fan motor insulation 
resistance
Insulation failure on the fan 
motor
Replace the fan motor.
Compressor relay on the 
relay board
Open circuit or insufficient 
contact surface area
Replace the relay board.
Compressor insulation
resistance
Insulation failure on
the compressor
Replace the compressor.