Steam Line Distribution Installation Manual | 8
Figure 5: Vertical Airflow
WARNING
These installation guidelines apply for duct velocities under 2000 ft/min (610 m/min), please
consult factory for higher velocities.
Please make sure no obstacles (elbow, filter, or diffuser) are located after the distributor in the
direction of the airflow closer than the absorption distance calculated for your application.
Unless you know the exact absorption distance required for the steam absorption into the air
steam, the distributor should be located at least 8-10 ft (2-3 m) away from any obstacle it may
condense on (elbow, diffuser, filter, etc.).