Nortec Steam Distribution User Manual

Page 6

Advertising
background image

3 | Steam Line Distribution Installation Manual

Table 1: Steam Line Material

Steam Hose

Copper Tube

Stainless Steel Tube

Short run < 10 feet (3 m)

Long run > 10 feet (3 m)

DI/RO Water

Table 2: Recommended Material and Size for Steam Run

Load

Steam Run

Steam Line Material

Steam Line Description

lb/hr

kg/hr

ft

m

0-30

0-13

0-10

0-3

Copper Tube

¾” MED-L Tubing (7/8” O.D)

0-30

0-13

10+

3+

Copper Tube

1” MED-L Tubing (1 1/8” O.D)

0-30

0-13

0-10

0-3

Stainless Steel Tube

7/8” Tube x 0.049” Thick

0-30

0-13

10+

3+

Stainless Steel Tube

1 1/8” Tube x 0.49” Thick

30-100

13-45

0-20

0-6

Copper Tube

1 ½” MED-L Tubing (1 5/8” O.D)

30-100

13-45

20+

6+

Copper Tube

2” MED-L Tubing (2 1/8” O.D.)

30-100

13-45

0-20

0-6

Stainless Steel Tube

1 ¾” Tube x 0.065” Thick

30-100

13-45

20+

6+

Stainless Steel Tube

2” Tube x 0.065” Thick

Please note that options shown in bold-italic font require that reducers be used at both ends. These extra-large sizes are to allow for
better condensation removal in long steam runs. These sizes will not permit you to use hose coupling to connect yourself to either
humidifier or distributors.



Table 3: Recommended Condensate Line at Distributor(s)

Dispersion Method

Condensate Hose

Copper Tube

Stainless Steel Tube

1 x Steam Distributor

3/8” Nortec 1328840

¼” MED-L Tubing (3/8” O.D.)

3/8” Tube 0.049 thick

3 x Steam Distributor

3/8” Nortec 1328840

½” MED-L Tubing (7/8” O.D.)

5/8” Tube 0.049” thick

* When using more than one distributor, the condensate line should be trapped before joined together.