Installation | 22

External Controls

Control Wiring

The following information is relevant to all controls, factory supplied or otherwise. For wiring use
a minimum of 18 AWG and keep as short as possible. The NHRS humidifier can be operated
with a modulating input or as On/Off.



Control Location

Figure 13: Control Location (Duct Humidification)

Duct Humidification

1 Air Proving Switch

Locate so that it can sense air flow, or lack thereof.

2 Duct High Limit

NHRS operates with On/Off control.

Locate at least 10 feet (3.0 m) from steam distributor, or far enough that steam is

fully absorbed under normal conditions.

3 Humidity Control

NHRS can be modulating, On/Off, or a humidity sensor.

Can be located either in return air duct (preferred) or in room being humidified.

Mount in area representative of room humidity (draft, doorways, sunlight, or

overhang such as shelf can affect reading). Avoid placing near discharge diffuser of
humidified air.

4 Outdoor Temperature Sensor

Mount in area representing outdoor air temperature (makeup air duct, outside).

Caution: Failure to wire the humidifier in accordance with the wiring instructions

could cause permanent damage. Such errors will void the warranty.