Troubleshooting | 54

Table 14: Troubleshooting errors and warnings (continued)

Malfunction / Indication

Cause

Remedy

Max. Boil down rate too long

Error code: 4A/4B

Error4B

SteamtimeAlarm

4Asteamtime

Individual heating elements faulty. Replace faulty heating elements.

Main voltage too low or failure of

a phase (L1, L2 or L3).

Replace fuses on power board.

Check main voltage and

connections.

Steam line too long or not

insulated.

Maintain maximum line lengths

(max. 15’). Insulate steam lines.

Max. Drain time exceeded

Error code: 5A/5B

Alarm5Adrain

Error5Bdrain

Drain pump not connected or

faulty.

Connect or replace drain pump.

Outlet line from unit kinked or

blocked.

Inspect outlet line from unit,

replace if necessary.

Water outlet blocked (external

outlet line or siphon blocked.

Clean water outlet line and

siphon.

Hose to level unit blocked.

Clean or replace hose.

Invalid level

Error code: 6A/6B

Alarm6A

Levelindicat

Error6B

levelindicat

Level unit faulty.

Replace level unit.

Magnetic field in vicinity of level

unit.

Eliminate magnetic field.

Steam pressure (error only)

Error code: 7A/7B

Alarm7A

communication

Steam hose blocked or restricted

(water trap).

Inspect steam hose, clean if

necessary and install correctly.

Pressure balance adapter into

steam connection fitting blocked.

Remove adapter and clean

opening with a needle.

Duct pressure too high

(>1500 Pa).

Inspect ventilation settings.

External safety chain

interrupted Error code: none

SafetychainexternalA

Mainsfailure B

Ventilator lock open.

Switch on ventilator/ventilation

system.

Automatic flow control has

responded.

Inspect ventilator/filter of

ventilation system.

Safeties are open.

Servicing, inspect system if

necessary.

Main failure on Unit B.

Inspect voltage supply to Unit B.