37 | Start Up

c. Check for correct functioning of the monitoring equipment (external safety

network).

d. Set the desired humidity value on the humidity controller / humidistat.
e. Make sure no leaks are present.

The heating current switches on as soon as the humidity controller / humidistat

demands humidity. The yellow LED lights and steam is produced after a short delay
(approximately 5 minutes).

2. The operating status is displayed in the LED on the unit as follows:

Table 8: NHRS Operational Status LEDs

LED

Action

Meaning

Green

Constant

Unit Producing Steam

Yellow

Flashing

Major or Minor Service Due.

Red

Flashing

The Unit is trying to self-correct a problem.

Red

Constant

Insoluble Problem

NOTE: Relevant data will be displayed on the NHRS LCD display during normal operation and
when in fault

3. If the humidifier is equipped with the optional Remote Fault Indication, the operating

status will be shown as follows:

Table 9: Remote Fault Indication

Relay

Description

Notes

K1

Steam

(N/O) Normally open

K2

Error

(N/O) Normally open Or (N/C) Normally closed

K3

Service

(N/O) Normally open Or (N/C) Normally closed

K4

Unit On

(N/O) Normally open