51 | Maintenance and Servicing

Major Maintenance









Major maintenance items include all those for the minor maintenance service, with the
exception that the steam tank must be cleaned at this point. The differences in maintenance
requirements are shown below.

Table 14: Minor and major maintenance

Maintenance Item

Unit has Scale

Management

System?

Minor

Maintenance

Interval

Major

Maintenance

Interval

Remove scale tank and empty

Yes

Required

Required

No

N/A

N/A

Remove steam tank - clean inside,

as well as heating elements

Yes

Optional

Required

No

Required

Required

Resetting Maintenance Indication (Major Maintenance Only)

1. Restore primary voltage to the unit.
2. With the unit in the “off” position, press and hold the drain activation switch.
3. Continue to hold the drain activation switch and turn the main power switch to the “on”

position.

4. Allow the unit to undergo initial startup diagnostics. When the diagnostics are complete,

release the drain activation switch. The unit maintenance should be cleared at this
point.

WARNING: A qualified service person should perform all maintenance on

the humidifier and any other equipment provided by Nortec that requires

maintenance.
NOTE: Instruction and details concerning the maintenance of the Nortec

equipment must be observed and adhered to without fail. Only the

maintenance documented in this manual must be carried out.