Description of setc outdoor specific components – Nortec SETC Outdoor User Manual

Page 7

Advertising
background image

Introduction | 4

Description of SETC Outdoor Specific Components

Table 1: SETC Outdoor Humidifier Components

Component

Function of Component

Auxiliary Drain
Outlet

Drains water from tank in case of pump failure or in case of fault or
power failure if freeze protection valve is installed.

Cabinet Drain

Drain outlet for integrated cabinet drain pan (outdoor unit only). Drain
to rooftop.

Cabinet Thermostat Sensor that activates the heaters if the cabinet temperature is too cold

for the electronics (will not prevent the tank and water components
from freezing).

Condensate Drain

Drains condensate formed from boiler steam in the heat exchanger(s).
(routed to pipe chase).

Drain Outlet

Drain port used for draining water from the humidifier tank.

Electrical Conduits

Two sealed conduits which provide a way for bringing electrical power
routed up through the pipe chase to an external disconnect.

Exhaust Fan

Cooling fan which is activated if the electrical cabinet gets too hot.

Fill Connection

1/2 in. NPT connection to the humidifier fill valve.

Freeze Protection

Valve

A normally open valve part of the freeze protection package. It allows

the tank to drain in case of power failure or in case of a fault when
humidifier operation cannot keep the humidifier warm enough to
prevent freezing.

Heater

Electrical cabinet heater used to keep electronics warm enough for
operation and cold weather start up only.

Lifting Hooks

Hooks provided for lifting the humidifier.

Mounting Panel

A panel provided on the outside of the humidifier for mounting a
dedicated external disconnect.

Outdoor Cabinet

An enclosure that provides protection from precipitation and allows the
SETC to be installed outdoors.

Outdoor Mounting
Base

An integrated support for the humidifier which includes a drain pan
(outdoor unit only), a pipe chase, and a means for curb mounting the
humidifier.

Pipe Chase

An opening in the outdoor cabinet’s drain pan which is used for routing
electrical power, controls, boiler steam, boiler condensate, fill water,
and drain water through the base of the humidifier.

Steam Inlet

Connection for boiler steam, it is connected to the heat exchangers.

Steam Outlet

Outlet for steam produced by the humidifier. Connect to steam line
with steam hose.

Note: See Humidifier Components on page 3 of the SE Series Installation manual for a