Steam Distributors Installation Manual | 8

C2

D

GO TO

Always align distributor holes so that steam is discharged
upwards to ensure condensate will remain in the distributor.

H

1/3W

2/3W

W

1/3W

1/3W 1/3W 1/3W

Min. W = 8” (203 mm)


















Figure 8: Vertical Airflow





Warning

These installation guidelines apply for duct velocities under 2000 ft/min

(610 m/min), please consult factory for higher velocities.

Please make sure no obstacles (elbow, filter, or diffuser) are located after

the distributor in the direction of the airflow closer than the absorption
distance calculated for your application.

Unless the exact absorption distance required for the steam absorption into

the air stream is known, the distributor should be located at least 8-10 ft
(2-3 m) away from any obstacle it may condense on (elbow, diffuser, filter,
etc.).