Steam Distributors Installation Manual | 6
Figure 5: Long Steam Run
GO TO
C2
- 45º
2
+ 45º
1
1 turn
3
B
Always align distributor holes so that steam is
discharged upwards to ensure condensate will
remain in the distributor.
Figure 6: Vertical Airflow
1 ft (30 cm)
min before turn
Condensate
tee every
15-20 ft
(4.5 - 6 m)
Condensate
tee at low
points
Individually trap multiple condensate
returns before joining on common line.
To Drain
Install condensate tee
before distributor
Method for Longer Runs With Limited Vertical Space
1 ft (30 cm)
min.